- 부하변화에 따른 hot-gas 바이패스 방식별 성능 비교
- ㆍ 저자명
- 백승문,윤정인,손창효,허정호,Baek. Seung-Moon,Yoon. Jung-In,Son. Chang-Hyo,Heo. Jung-Ho
- ㆍ 간행물명
- 한국동력기계공학회지
- ㆍ 권/호정보
- 2014년|18권 5호|pp.48-54 (7 pages)
- ㆍ 발행정보
- 한국동력기계공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In this paper, three refrigeration systems bypassing hot-gas to compressor outlet, compressor and condenser outlet and evaporator inlet are theoretically compared to offer basic design data for performance depending on cooling load using a HYSYS program. The main results are summarized as follows : First, the COP of third system is the highest. Next, the COP of second system is higher than first one. And, the temperature of compressor inlet of third system is constant for all cooling load. Compared to first and second system, the compressor inlet temperature of the first system is higher than second one for all cooling loads. From the above results, third system, which is bypassing hot-gas to evaporator inlet, is more advantageous when considering the precise temperature control and excellent performance of oil and water cooler of industrial machine.