- 온라인 변압기 부분방전 측정기법 적용
- ㆍ 저자명
- 권동진,Kweon. Dong-Jin
- ㆍ 간행물명
- 전기학회논문지. The transactions of the Korean Institute of Electrical Engineers. C/ C, 전기물성·응용부문
- ㆍ 권/호정보
- 2001년|50권 8호|pp.394-400 (7 pages)
- ㆍ 발행정보
- 대한전기학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This paper describes an application of the on line partial discharge measurement method in operating transformer. In the operating transformer, the partial discharge signal may be superimposed by radio intereference voltage(RIV) and pulse shaped noise signals generated by external corona. The partial discharge quantity showed about 3,800pC due to very high sinusoidal interferences at the measuring impedance terminal of the transformer bushing tap. In order to reject these noises, this paper applied RIV filter, band-pass filters and noise gating method. The resulting measuring sensitivity was improved from 3,800pC to 160pC.