- 화재감지 센서 작동시간 및 열방출률에 대한 실험연구
- ㆍ 저자명
- 홍성호,Hong. Sung-Ho
- ㆍ 간행물명
- 전기학회논문지= The Transactions of the Korean Institute of Electrical Engineers
- ㆍ 권/호정보
- 2012년|61권 9호|pp.1358-1361 (4 pages)
- ㆍ 발행정보
- 대한전기학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This paper presents a study on the analysis for activation time and threshold value of heat detection sensor using HRR(Heat Release Rate). And it is represented to quantity of heat to activate heat detection sensor. The experiment is conducted to measure activation time and HRR of fire detection sensor burning alcohol and n-heptane. In order to burn the alcohol and n-heptane using $43.5cm(L){ imes}43.5cm(W){ imes}5cm(D)$ and $33cm(L){ imes}33cm(L){ imes}5cm(D)$ steel pan and the quantity of alcohol and n-heptane are 2.5 L and 650 g, respectively. The results show that peak HRR are in case of alcohol 66.13 kW and in case of n-heptane 151.64 kW, respectively. Total heat releases of heat detection sensor are in case of alcohol approximately 20.7 MJ and in case of n-heptane approximately 18 MJ, respectively.