- 데이터 센터의 외기냉수냉방 시스템에 대한 에너지 절감효과 분석
- ㆍ 저자명
- 윤정인,손창효,허정호,김영민,Yoon. Jung-In,Son. Chang-Hyo,Heo. Jeong-Ho,Kim. Young-Min
- ㆍ 간행물명
- 한국동력기계공학회지
- ㆍ 권/호정보
- 2014년|18권 3호|pp.73-78 (6 pages)
- ㆍ 발행정보
- 한국동력기계공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
Recently, Free cooling system usage has increased at many buildings in intermediate and winter season. Free cooling system is used to reduce the energy consumption of refrigeration in that season. Free cooling system is refrigeration system using cooled water. In general, this system is applied with the building having refrigeration load at all time such as a data center. In this study, energy consumption of a data center taking free cooling system in Ulsan was evaluated by the software HYSYS. the main result is as in the following : free cooling system is effective from January to April and from November to December. In case of Ulsna in 2013, using free coolng system is able to spend refrigeration energy of about 15% less than existing system. According to this result, it is appropriated that free cooling system is used in building having refrigeration load at all time such as data center.